  4. Achieving dispatchability in data centers: carbon and cost-aware sizing of energy storage and local photovoltaic generation
 
research article

Achieving dispatchability in data centers: carbon and cost-aware sizing of energy storage and local photovoltaic generation

Figini, Enea  
•
Paolone, Mario  
September 2025
Sustainable Energy, Grids and Networks

Data centers are large electricity consumers due to the high consumption needs of servers and their cooling systems. With the rapid growth of crypto-currency and artificial intelligence, their electricity consumption is expected to increase substantially. With the electricity sector being responsible for a large share of global greenhouse gas (GHG) emissions, it is important to lower the carbon footprint of data centers to meet GHG emissions targets set by international agreements. Moreover, uncontrolled data center integration into power distribution grids increases the stochasticity of electricity demand, thus increasing the need for reserve capacity and leading to operational inefficiencies and higher emissions. This work provides a method to size a PhotoVoltaic (PV) system and an Energy Storage System (ESS) for an existing data center looking to reduce both its carbon footprint and demand stochasticity through day-ahead dispatching. A scenario-based optimization framework is developed to jointly size the PV and ESS, minimizing the expected operational and capital expenditures and the carbon footprint of the data center complex. The model considers the life cycle assessments (LCA) of the systems and the dynamic carbon intensity of the upstream electricity supply. Case studies in different Swiss cantons and regions of Germany emphasize the need for location-aware sizing processes since the obtained optimal solutions strongly depend on the local electricity carbon footprint and on the irradiance conditions. The maximum carbon footprint reduction reaches approximately 50 % in Germany and 4 % in Switzerland. Installed power generation and energy storage capacities vary by up to 36 times across regions.

  • Files
  • Details
  • Metrics
Type
research article
DOI
10.1016/j.segan.2025.101920
Author(s)
Figini, Enea  

EPFL

Paolone, Mario  

EPFL

Date Issued

2025-09

Publisher

Elsevier BV

Published in
Sustainable Energy, Grids and Networks
Volume

43

Start page

101920

Subjects

Data center

•

Battery energy storage

•

Sizing

•

Multi-objective stochastic optimization

•

Carbon emissions

•

Dispatchability

•

Power distribution

Editorial or Peer reviewed

REVIEWED

Written at

EPFL

EPFL units
DESL  
FunderFunding(s)Grant NumberGrant URL

EPFL

HeatingBits

https://heatingbits.epfl.ch
Available on Infoscience
August 15, 2025
Use this identifier to reference this record
https://infoscience.epfl.ch/handle/20.500.14299/252903
Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés