  4. A Review of On-Chip Micro-Evaporation: Experimental Evaluation of Liquid Pumping and Vapor Compression Driven Cooling Systems and Control
 
research article

A Review of On-Chip Micro-Evaporation: Experimental Evaluation of Liquid Pumping and Vapor Compression Driven Cooling Systems and Control

Marcinichen, Jackson Braz  
•
Olivier, Jonathan Albert
•
Oliveira, Vinícius de
Show more
2011
Applied Energy

Thermal designers of data centers and server manufacturers are showing a greater concern regarding the cooling of the new generation data centers, which consume considerably more electricity and dissipate much more waste heat, a situation that is creating a re-thinking about the most effective cooling systems for the future beyond conventional air cooling of the chips/servers. A potential significantly better solution is to make use of on-chip two-phase cooling, which, besides improving the cooling performance at the chip level, also adds the capability to reuse the waste heat in a convenient manner, since higher evaporating and condensing temperatures of the two-phase cooling system (from 60-95°C) are possible with such a new “green” cooling technology. In the present project, two such two-phase cooling cycles using micro-evaporation technology were experimentally evaluated with specific attention being paid to (i) controllability of the two-phase cooling system, (ii) energy consumption and (iii) overall exergetic efficiency. The controllers were evaluated by tracking and disturbance rejection tests, which were shown to be efficient and effective. The average temperatures of the chips were maintained below the limit of 85°C for all tests evaluated in steady state and transient conditions. In general, simple SISO strategies were sufficient to attain the requirements of control. Regarding energy and exergy analyses, the experimental results showed that both systems can be thermodynamically improved since only about 10% of the exergy supplied is in fact recovered in the condenser in the present setup.

  • Files
  • Details
  • Metrics
Type
research article
DOI
10.1016/j.apenergy.2011.10.030
Web of Science ID

WOS:000300463800016

Author(s)
Marcinichen, Jackson Braz  
Olivier, Jonathan Albert
Oliveira, Vinícius de
Thome, John Richard  
Date Issued

2011

Published in
Applied Energy
Volume

92

Start page

147

End page

161

Subjects

Data center

•

Microprocessor

•

On-chip two-phase cooling cycle

•

Micro-evaporator

•

Controller

Editorial or Peer reviewed

REVIEWED

Written at

EPFL

EPFL units
LTCM  
LA  
Available on Infoscience
November 30, 2011
Use this identifier to reference this record
https://infoscience.epfl.ch/handle/20.500.14299/72918
Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés