Loading...
conference paper not in proceedings
Intube Flow Boiling of R–502 and Two Near-Azeotropic Alternatives.
1994
Flow boiling experiments for two new non-azeotropic, three-component refrigerant mixtures (HP80 and HP62) and R-502 have been carried out inside a 12 mm bore, horizontal tube. Local boiling coefficients for HP62 are slightly larger that those for R-502 under the same test conditions while those for HP80 are slightly smaller. The heat transfer performances of the three fluids are accurately predicted by an existing flow boiling correlation modified here to include a nucleate pool boiling mixture equation.
Loading...
Name
LENI-94-03.pdf
Access type
restricted
Size
427.16 KB
Format
Adobe PDF
Checksum (MD5)
69619d63424ad19c42c7617b29f6dd69