The paper presents a fault location procedure for distribution networks based on the wavelet analysis of the fault-generated traveling waves. In particular, the proposed procedure implements the continuous wavelet analysis applied to the voltage waveforms recorded during the fault in correspondence of a network bus. In order to improve the wavelet analysis, an algorithm is proposed to build specific mother wavelets inferred from the fault-originated transient waveforms. © 2008 IEEE.