Experimental investigation of a direct driven radial compressor for domestic heat pumps
The presence of oil in domestic heat pumps is an obstacle toward higher efficiency, particularly for enhanced surface evaporators and for advanced concepts based on two- stage cycles. Very compact direct driven radial compressors supported on oil-free bearings represent a promising alternative. This paper presents the derivation of the specifications, the choice for an appropriate refrigerant fluid and the design of a proof of concept proto-type with the various tradeoffs between the impeller characteristics to follow the seasonal heat demand, the bearing and rotordynamics for a stable operation. Heat pump simulation results, the design of the impeller as well as the layout of the experimental facility and first experimental results are presented. An impeller with a tip diameter of 20 mm has been tested at rotational speeds of up to 210 krpm reaching pressure ratios in excess of 3.3 and efficiencies above 78%. The refrigerant chosen for this first experimental approach is HFC 134a.
Experimental investigation of a direct driven radial compressor for domestic heat pumps.pdf
restricted
866.41 KB
Adobe PDF
fed316edc8e9824794bb783ab79db957