Applications of a robust state estimator to the EEF power system

The EEF utility, which has its headquarters in Fribourg, Switzerland, is planning to install in its new energy management system a robust Schweppe-type Huber GM-state estimator (SHGM). Prior to the installation, the iterative algorithm that implements the estimator has been upgraded to meet the specifications and extensive offline simulations have been carried out on the EEF power network. This power system consists of 3 islands and 33 substations that are interconnected by 60 kV subtransmission lines. The islands may from time to time be interconnected. Simulations revealed that the SHGM algorithm exhibits excellent convergence properties and is robust to bad measurements, be they leverage points or not. Installation of the state estimator on the computer facilities located at the new EEF control center will take place in the summer of 1998, followed by its full real-time testing


Published in:
LESCOPE 98. 1998 Large Engineering Systems Conference on Power Engineering. Conference Proceedings. Theme: Powering up to 2000, 20 - 4
Year:
1998
Keywords:
Note:
power systems;robust state estimator;Switzerland;Schweppe-type Huber GM-state estimator;energy management system;iterative algorithm;offline simulations;subtransmission lines;control simulation;substations;power network interconnections;computer simulation;convergence properties;SHGM algorithm;60 kV;