Break-even Distance for MVDC Electricity Networks According to Power Loss Criteria
2021
2021 23Rd European Conference On Power Electronics And Applications (Epe'21 Ecce Europe)
The medium voltage direct current (MVDC) technology is emerging in electricity networks includingpoint-to-point transmission, distribution networks and collection networks for renewable energysources. In this article the MVDC break-even distance (with respect to AC distribution) is calculatedaccording to the overall energy efficiency criteria. The break-even distance is found to vary from lessthan 10 km to several tens of kilometers depending on power and voltage ratings and network topology.