  4. Time reversal applied to fault location in power networks: Pilot test results and analyses
 
research article

Time reversal applied to fault location in power networks: Pilot test results and analyses

Wang, Zhaoyang
•
Razzaghi, Reza
•
Paolone, Mario
Show more
2020
Electrical Power and Energy Systems

This paper presents the results of a pilot test performed on a real medium voltage distribution network in Switzerland with the aim of assessing the performance of a fault location system relying on the Electromagnetic Time Reversal (EMTR) method. To the best of the Authors’ knowledge, this is the first time that the EMTR-based fault location technique is validated through live tests. The pilot network is a live radial medium voltage distribution feeder, which consists of 11.9-km long double-circuit lines operating at 18/60 kV and multiple 18-kV three-phase laterals. The branched lines are overhead lines, underground cables, or mixed configuration with lengths ranging from tens of meters to a few kilometers. The test involves solid- and resistive-type single-phaseto- ground fault occurrences triggered along one of the laterals when the network is operational. The fault location task is performed by a real-time industrial controller prototype that integrates the functions of fault detection, data acquisition, time-reversal processing and Electromagnetic Transients simulations. Concerning the methodological aspects, the EMTR Fault Current Signal Energy (FCSE) metric is used to determine the location of the fault. The obtained results show that the FCSE metric is capable of accurately identifying the faulty phase and the real fault location in all tested fault cases, with a location accuracy of less than 10 m.

  • Details
  • Metrics
Type
research article
DOI
10.1016/j.ijepes.2019.105382
Author(s)
Wang, Zhaoyang
Razzaghi, Reza
Paolone, Mario
Rachidi, Farhad
Date Issued

2020

Published in
Electrical Power and Energy Systems
Volume

114

Article Number

105382

Subjects

Electromagnetic time reversal

•

Distribution networks

•

Fault location

•

Pilot tests

Editorial or Peer reviewed

REVIEWED

Written at

EPFL

EPFL units
SCI-STI-FR  
DESL  
Available on Infoscience
July 15, 2019
Use this identifier to reference this record
https://infoscience.epfl.ch/handle/20.500.14299/159135
Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés