Repository logo

Infoscience

  • English
  • French
Log In
Logo EPFL, École polytechnique fédérale de Lausanne

Infoscience

  • English
  • French
Log In
  1. Home
  2. Academic and Research Output
  3. Conferences, Workshops, Symposiums, and Seminars
  4. Hybrid Two-Phase Cooling Technology For Next-Generation Servers: Thermal Performance Analysis
 
conference paper

Hybrid Two-Phase Cooling Technology For Next-Generation Servers: Thermal Performance Analysis

Amalfi, Raffaele L.
•
Faraldo, Francois P.
•
Salamon, Todd
Show more
January 1, 2021
Proceedings Of The Twentieth Intersociety Conference On Thermal And Thermomechanical Phenomena In Electronic Systems (Itherm 2021)
20th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm)

This paper advances the work presented at ITHERM 2020 where a novel passive two-phase technology was introduced for more efficient cooling of datacenters compared to air-based cooling solutions (e.g. In-Room, In-Row, etc.). The proposed hybrid two-phase cooling technology uses passive low-height thermosyphons to dissipate the heat generated by high power components inside the servers. The heat is then transferred to multiple rack-level thermosyphons, equipped with one or more overhead compact condensers, which in turn dissipate the total heat from the rack into a room-level water-based or air-based cooling loop. Air-cooling is still used for the low heat-generating components (e.g. memory units, secondary chips, etc.) to make the cooling technology cost effective.

This study is focused on a thermal performance analysis of the hybrid two-phase cooling technology applied to a single server (2U HP ProLiant DL180 G6), where low-height thermosyphons are installed to cool the two CPUs, and the remaining server components are cooled via air in forced convection using server-level fans. The thermal performance of the low-height thermosyphons is extracted from previous experimental measurements carried out at Nokia Bell Labs and presented at ITHERM 2020. Additional measurements considering the effect of the refrigerant charge on the thermal resistance and associated chip case temperature are conducted. The air-cooling performance and flow distribution are investigated via CFD simulations performed in COMSOL that characterize the conjugate heat transfer between server components and cooling air. The experimental and numerical results presented here show that, at the maximum server IT load of 587 W, the hybrid two-phase technology ensures sufficient cooling for all the hardware components while significantly reducing the energy consumption of the fans. Specifically, the fan contribution is reduced from 24% (traditional air-cooling) to about 2% of the server effective IT load (hybrid two-phase cooling), demonstrating the potential of the proposed technology to scale existing hardware and build next-generation datacenters, while keeping low costs and being environmentally-friendly.

  • Details
  • Metrics
Type
conference paper
DOI
10.1109/ITherm51669.2021.9503288
Web of Science ID

WOS:000703033800052

Author(s)
Amalfi, Raffaele L.
Faraldo, Francois P.
Salamon, Todd
Enright, Ryan
Cataldo, Filippo  
Marcinichen, Jackson B.
Thome, John R.  
Date Issued

2021-01-01

Publisher

IEEE

Publisher place

New York

Published in
Proceedings Of The Twentieth Intersociety Conference On Thermal And Thermomechanical Phenomena In Electronic Systems (Itherm 2021)
ISBN of the book

978-1-7281-8539-2

Series title/Series vol.

InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems

Start page

423

End page

430

Subjects

Thermodynamics

•

Engineering, Electrical & Electronic

•

Engineering, Mechanical

•

Engineering

•

datacenters

•

passive two-phase heat transfer

•

refrigerants

•

supplemental air-cooling

•

thermal performance

•

thermosyphons

Editorial or Peer reviewed

REVIEWED

Written at

EPFL

EPFL units
LTCM  
Event nameEvent placeEvent date
20th InterSociety Conference on Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm)

ELECTR NETWORK

Jun 01-04, 2021

Available on Infoscience
October 23, 2021
Use this identifier to reference this record
https://infoscience.epfl.ch/handle/20.500.14299/182465
Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés