Repository logo

Infoscience

  • English
  • French
Log In
Logo EPFL, École polytechnique fédérale de Lausanne

Infoscience

  • English
  • French
Log In
  1. Home
  2. Academic and Research Output
  3. Conferences, Workshops, Symposiums, and Seminars
  4. INFLUENCE OF THE SATURATION TEMPERATURE ON THE HEAT TRANSFER COEFFICIENT FOR FLOW BOILING INSIDE HORIZONTAL SMOOTH TUBES
 
conference paper not in proceedings

INFLUENCE OF THE SATURATION TEMPERATURE ON THE HEAT TRANSFER COEFFICIENT FOR FLOW BOILING INSIDE HORIZONTAL SMOOTH TUBES

da Silva Lima, Ricardo J.  
•
Bandarra Filho, Enio P.
•
Thome, John R.  
2008
EBECEM 2008 - 1º Encontro Brasileiro sobre Ebulição, Condensação e Escoamento Multifásico Líquido-Gás

This article presents experimental results of heat transfer from two different studies [1, 2] for horizontal flow boiling inside smooth copper tubes with different refrigerants. The main goal of this study was to verify the influence of the saturation temperature on the heat transfer coefficient. The experimental tests were carried for refrigerants R-134a, R-22 and R-404A, at saturation temperatures ranging from 5 to 20°C for two tubes of 12.7 and 13.84 mm ID and three heat fluxes of 5, 7.5 and 17.5 kW/m2. The vapor quality ranged from 5 to 90% and the mass velocity was 300 kg/s.m2. Under these conditions the heat transfer coefficient shows an interesting trend: it behaves differently, in function of the saturation temperature, in the nucleate and convective boiling dominated regions. In the nucleate boiling dominated region the heat transfer coefficient increases with the saturation temperature. In the convective boiling dominated region this phenomenon is inverted, that is, the heat transfer coefficient decreases with the saturation temperature. This phenomenon was verified through the concept of the thermal resistance of the liquid thickness. Since the heat transfer coefficient is proportional to the inverse of the thermal resistance of the liquid film, it increases with decreasing saturation temperature. The transition between nucleate and convective boiling dominated regions, denominated by [1] as a local minimum of the heat transfer coefficient, was also clearly observed with all the refrigerants.

  • Details
  • Metrics
Type
conference paper not in proceedings
Author(s)
da Silva Lima, Ricardo J.  
Bandarra Filho, Enio P.
Thome, John R.  
Date Issued

2008

Editorial or Peer reviewed

NON-REVIEWED

Written at

EPFL

EPFL units
LTCM  
Event nameEvent placeEvent date
EBECEM 2008 - 1º Encontro Brasileiro sobre Ebulição, Condensação e Escoamento Multifásico Líquido-Gás

Florianópolis, Brasil

28-29 April 2008

Available on Infoscience
April 21, 2008
Use this identifier to reference this record
https://infoscience.epfl.ch/handle/20.500.14299/23391
Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés