Minkowski Distance Based Pilot Protection for Tie Lines Between Offshore Wind Farms and MMC

Yang, Zhe
•
Zhu, Ruijin
•
Liao, Wenlong  
June 1, 2024
IEEE Transactions on Industrial Informatics

Offshore wind farms (OWFs) with modular multilevel converter high-voltage dc (MMC-HVdc) have become an important form of renewable energy utilization. However, if a fault occurs at the tie line between the MMC and the OWF, the fault steady-state current at the fault point will be equal to zero when the negative-sequence current is suppressed, so traditional differential protection may fail to operate. To cope with this issue, this article proposes a new pilot protection method based on Minkowski distance. For internal faults, OWF and MMC will have different transient currents, so the Minkowski distance will be much higher than 0, but it will be equal to 0 for external faults and normal operation since the fault currents on both sides are the opposite. Therefore, the internal fault can be detected reliably. The proposed method does not depend on the power frequency phasor extraction, so it is not affected by the frequency offset in the transient process. In addition, this method operates quickly and has a strong ability to withstand fault resistance and environmental noise. Moreover, since there is always a transient process when a fault occurs, the proposed method applies to different fault ride-through strategies. PSCAD simulation and real-time digital simulator experiments show that the proposed method is suitable for different fault locations and types.

  • Details
  • Metrics
Type
research article
DOI
10.1109/TII.2024.3369668
Scopus ID

2-s2.0-85188726398

Author(s)
Yang, Zhe
Zhu, Ruijin
Liao, Wenlong  

École Polytechnique Fédérale de Lausanne

Date Issued

2024-06-01

Published in
IEEE Transactions on Industrial Informatics
Volume

20

Issue

6

Start page

8441

End page

8452

Subjects

Minkowski distance

•

offshore wind farms (OWFs)

•

pilot protection

•

transient current

Editorial or Peer reviewed

REVIEWED

Written at

EPFL

EPFL units
WIRE  
Available on Infoscience
January 16, 2025
Use this identifier to reference this record
https://infoscience.epfl.ch/handle/20.500.14299/242920
Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés