Under Frequency Load Shedding based on PMU Estimates of Frequency and ROCOF
The paper describes a local under-frequency load shedding and load restoration scheme, that exploits frequency and Rate-of-Change-of-Frequency (ROCOF) measurements produced by Phasor Measurement Units (PMUs) as detectors of a large contingency. The paper further discusses the appropriateness of using the synchrophasor model for estimating ROCOF during fast transients following a severe generation-load imbalance. The performance of the proposed relaying scheme is compared with a frequency-only based strategy, by means of a real-time digital simulator implementing the time-domain full-replica model of the IEEE 39 bus system.
WOS:000458690200026
2018-01-01
978-1-5386-4505-5
New York
IEEE PES Innovative Smart Grid Technologies Conference Europe
REVIEWED
Event name | Event place | Event date |
Sarajevo, BOSNIA & HERCEG | Oct 21-25, 2018 | |