Enhancing Two-Phase Cooling Efficiency through Thermal- Aware Workload Mapping for Power-Hungry Servers

Iranfar, Arman  
•
Pahlevan, Ali  
•
Zapater Sancho, Marina  
Show more
2019
Proceedings of the IEEE/ACM 2019 Design, Automation, and Test in Europe (DATE) Conference
IEEE/ACM 2019 Design, Automation, and Test in Europe (DATE) Conference

The power density and, consequently, power hungriness of server processors is growing by the day. Traditional air cooling systems fail to cope with such high heat densities, whereas single-phase liquid-cooling still requires high mass flowrate, high pumping power, and large facility size. On the contrary, in a micro-scale gravity-driven thermosyphon attached on top of a processor, the refrigerant, absorbing the heat, turns into a two-phase mixture. The vapor-liquid mixture exchanges heat with a coolant at the condenser side, turns back to liquid state, and descends thanks to gravity, eliminating the need for pumping power. However, similar to other cooling technologies, thermosyphon efficiency can considerably vary with respect to workload performance requirements and thermal profile, in addition to the platform features, such as packaging and die floorplan. In this work, we first address the workload- and platform-aware design of a two-phase thermosyphon. Then, we propose a thermal-aware workload mapping strategy considering the potential and limitations of a two-phase thermosyphon to further minimize hot spots and spatial thermal gradients. Our experiments, performed on an 8-core Intel Xeon E5 CPU reveal, on average, up to 10ºC reduction in thermal hot spots, and 45% reduction in the maximum spatial thermal gradient on the die. Moreover, our design and mapping strategy are able to decrease the chiller cooling power at least by 45%.

  • Files
  • Details
  • Metrics
Loading...
Thumbnail Image
Name

699_OutputPaper(2).pdf

Access type

openaccess

License Condition

CC BY

Size

3.23 MB

Format

Adobe PDF

Checksum (MD5)

8cb74f1ad2dff8c2545ce3cd5bcdf730

Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés