Nucci, Carlo AlbertoBorghetti, AlbertoPaolone, MarioBorselli, PietroBernardi, MarinaMalgarotti, StefanoMastandrea, Ignazio2012-07-202012-07-202012-07-202004https://infoscience.epfl.ch/handle/20.500.14299/84050Recent power quality studies have been focused on the source-identification of voltage disturbances at distribution network busses. This paper describes a method aimed at correlating indirect-lightning events with power systems relay operations, associated with voltage dips. The proposed method, based on the coordinated use of the Italian lightning location system CESI-SIRF, the Italian monitoring system of protection manoeuvres CESI-SAM, and the availability of an advanced simulation tool for the accurate simulation of lightning-induced voltages on complex power networks, namely the LIOVEMTP code, is applied to the real case of an Italian distribution system. The LIOV-EMTP code is also employed along with a statistical procedure based on the Monte Carlo method to carry out a statistical analysis aimed at assessing the lightning performance of a typical Italian distribution line.lightning-induced overvoltageslightning location systemspower qualityvoltage dip/sagLightning-Induced Voltages on Overhead Distribution Lines: Theoretical and Experimental Investigation of Related Problems and their Impact on Power Qualitytext::conference output::conference paper not in proceedings