Siemaszko, DanielRufer, Alfred2013-05-062013-05-06201310.1109/PEDS.2013.6527213https://infoscience.epfl.ch/handle/20.500.14299/91987WOS:000325946200230The handling of weak networks with asymmetric disturbances implies the accurate handling of the second harmonic component appearing under unbalanced networks. This paper proposes a two-step approach using classic vector control for operating the current controller from the network disturbance. First, both voltage and current must be described in the positive and negative sequence with a proper decoupling. The use of a double frame controller for forcing current balance proves to drastically reduce the second harmonic component in the DC-link voltage. As a second step, a current reference computing method is proposed for fully compensating power oscillations on the DC side that is applicable for phase voltage dips up to 50%.asymmetric networkweak networkPLLdouble frame controlvector controlpower theoryPower Compensation Approach and Double Frame Control for Grid Connected Converterstext::conference output::conference proceedings::conference paper