Becker, JohannaKettner, Andreas MartinPaolone, Mario2025-01-312025-01-312025-04-242025-01-302025-01-2710.1109/TSG.2025.3532571https://infoscience.epfl.ch/handle/20.500.14299/246056In Part I of this paper a method for the Harmonic Stability Assessment (HSA) of power systems with a high share of Converter-Interfaced Distributed Energy Resources (CIDERs) was proposed. Specifically, the Harmonic State-Space (HSS) model of a generic power system is derived through combination of the components’ HSS models. The HSS models of CIDERs and grid are based on Linear Time-Periodic (LTP) models, capable of representing the coupling between different harmonics. In Part II, the HSA of a grid-forming, and two grid-following CIDERs (i.e., ex-and including the DC-side modelling) is performed. More precisely, the classification of the eigenvalues, the impact of the maximum harmonic order on the locations of the eigenvalues, and the sensitivity curves of the eigenvalues w.r.t. to control parameters are provided. These analyses allow to study the physical meaning and origin of the CIDERs’ eigenvalues. Additionally, the HSA is performed for a representative example system derived from the CIGR’E low-voltage benchmark system. A case of harmonic instability is identified through the system eigenvalues, and validated with Time-Domain Simulations (TDS) in Simulink. It is demonstrated that, as opposed to stability analyses based on Linear Time-Invariant (LTI) models, the HSA is suitable for the detection of harmonic instability.enharmonic analysiseigenvalue analysisdistributed energy resourcesharmonic stability assessmentsensitivity analysisConverted interfaced resourcesHarmonic Stability Analysis of Microgrids with Converter-Interfaced Distributed Energy Resources, Part II: Case Studiestext::journal::journal article::research article