High temperature heat pump using HFO and HCFO refrigerants – system design and experimental results

High temperature heat pumps (HTHP) with heat sink temperatures of 100 to 160 °C will increasingly become commercialized in the coming years, especially for industrial drying, sterilization and evaporation processes. In particular, the HFO R1336mzz(Z) and the HCFOs R1233zd(E) & R1224yd(Z) are low GWP replacement refrigerants for R245fa and R365mfc. This study examines the experimental performance of R1336mzz(Z) and R1233zd(E) in a laboratory HTHP with 5 to 10 kW heating capacity. The developed heat pump is single-stage, operates with a variable speed piston compressor, and contains a continuously adjustable internal heat exchanger (IHX) for superheating control. The performance data were measured at 30, 50, and 70 K temperature lift (40 to 80°C heat source, 80 to 150°C heat sink). At W60/W110, the experimental results with R1233zd(E) showed a COP of 2.8 (basic cycle) and 3.1 with IHX integration (+15%). For R1336mzz(Z) a COP of 2.4 and 3.0 was reached (+24%). By increasing the heat sink temperature glide from 5 to 30 K, a further 15% COP increase was achieved.


Published in:
[Proceedings of ICR 2019]
Presented at:
ICR 2019 - The 25th IIR International Congress of Refrigeration, Montréal, Québec, Canada, August 24-30, 2019
Year:
Aug 25 2019
Laboratories:




 Record created 2019-09-09, last modified 2019-09-11


Rate this document:

Rate this document:
1
2
3
 
(Not yet reviewed)