Evaluation of Power System Lightning Performance, Part I: Model and Numerical Solution Using the PSCAD-EMTDC Platform
The paper addresses the important issue of evaluating the overvoltages produced on a power system by a lightning event. First, the theoretical formulation of the problem in the time domain is presented. Then its numerical solution together with its implementation is described. Finally, a PSCAD-EMTDC interface and platform is developed, which allows us to model a realistic network, automatically distinguish between direct and indirect strokes and account for power network precontingency conditions. The obtained results are compared with a frequency-domain solution for a simple case in order to validate the finite-difference time-domain method adopted to solve the coupling equations and the interface with PSCAD. The comparison with the well-known LIOV code for a more complex case is used as a general validation of the overall tool. In a companion paper, the developed platform will be used to evaluate the lightning performance of a portion of the Italian MV distribution network.
Cite this item
Brignone, M., Delfino, F., Procopio, R., Rossi, M., & Rachidi, F. (2017). Evaluation of Power System Lightning Performance, Part I: Model and Numerical Solution Using the PSCAD-EMTDC Platform. IEEE Transactions on Electromagnetic Compatibility, 59(1), 137–145. https://doi.org/10.1109/TEMC.2016.2601640
Click Copy to copy the citation, or select the text manually.
WOS:000387359700016
2017
59
1
137
145
REVIEWED
EPFL