Impact of Grid Asymmetries on the Operation and Capacitive Energy Storage Design of Modular Multilevel Converters

The grid-connected modular multilevel converter (MMC) is very likely to operate under asymmetric grid conditions. Such a converter features several unique characteristics, whichmake its analysis different from other types of power converters in similar cases. In this paper, the three well-established control techniques, i. e., balanced current and negative sequence current injection for active/reactive power oscillation elimination, are tailored for the MMC case taking into account grid current limitation under fault conditions. Since the focus is laid on the MMC design impact during grid asymmetries, the three methods are compared in terms of branch energy variation increase as well as maximum achievable active power transfer. Moreover, the effect of circulating current second-order harmonic injection for capacitive storage reduction as well as dc-link oscillation elimination is also studied. Finally, experimental results from a downscaled laboratory prototype verify the theoretical studies.


Published in:
Ieee Transactions On Industrial Electronics, 62, 11, 6697-6707
Year:
2015
Publisher:
Piscataway, Institute of Electrical and Electronics Engineers
ISSN:
0278-0046
Keywords:
Laboratories:




 Record created 2015-12-02, last modified 2018-12-03