  4. Impact of Frequency-Dependent Soil Models on Grounding System Performance for Direct and Indirect Lightning Strikes
 
Loading...
Thumbnail Image
research article

Impact of Frequency-Dependent Soil Models on Grounding System Performance for Direct and Indirect Lightning Strikes

Nazari, Moein
•
Moini, Rouzbeh
•
Fortin, Simon
Show more
2021
IEEE Transactions on Electromagnetic Compatibility

The goal of this article is to investigate the effect of frequency-dependent soil models on the performance of grounding electrodes subjected to lightning strikes. Several soil models are examined while accounting for the variation of soil resistivity and permittivity as a function of the lightning current frequency spectrum. The analysis is performed for a homogeneous soil and a two-layer horizontally stratified soil. The impact of the frequency-dependent soil parameters on the ground potential rise (GPR) of simple grounding electrodes subjected to lightning is analyzed and discussed. The analysis is performed in the frequency domain and in the time domain. A wind turbine and its grounding system are also considered in this article. Special attention is given to the case of indirect lightning, rarely mentioned in the literature. The GPR of the grounding electrodes is examined when the frequency dependence of the soil is taken into account and the lightning channel is located at close distances to the electrodes. Indeed, the level of induced electromagnetic fields caused by a nearby lightning channel can still be too high and potentially dangerous. The computations are performed using an efficient Method of Moments (MoM) numerical tool based on surface-wire integral equations for a stratified medium in the frequency range from dc to several MHz. Numerical results demonstrate that the frequency dependency of the soil parameters results in a decrease of the potential rise of the grounding electrodes, with respect to the case where the parameters are assumed constant.

  • Details
  • Metrics
Type
research article
DOI
10.1109/TEMC.2020.2986646
Author(s)
Nazari, Moein
•
Moini, Rouzbeh
•
Fortin, Simon
•
Dawalibi, Farid P.
•
Rachidi, Farhad  
Date Issued

2021

Published in
IEEE Transactions on Electromagnetic Compatibility
Volume

63

Issue

1

Start page

134

End page

144

Peer reviewed

REVIEWED

Written at

EPFL

EPFL units
SCI-STI-FR  
Available on Infoscience
February 19, 2021
Use this identifier to reference this record
https://infoscience.epfl.ch/handle/20.500.14299/175381
Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés