Fire performance of water-cooled GFRP columns. Part I: Fire endurance investigation

Bai, Y.  
•
Hugi, E.
•
Ludwig, C.
Show more
2011
Journal of Composites for Construction

Structural fire endurance experiments were conducted on full-scale cellular glass fiber-reinforced (GFRP) columns under axial compression and subjected to ISO834 fire exposure from one side. Unprotected columns can resist fire for more than 30 min, which is sufficient for occupants to be evacuated from smaller buildings. The closed cellular cross-section prevented the rapid heating of the webs, which could therefore continue stabilizing the face sheet on the cold side against buckling. Water cooling was proven to offer an effective active fire-protection system. The structural function of the column could be maintained for two hours. Previously developed models were capable of accurately predicting the time-dependent temperature responses, modulus degradation, and time to failure. DOI: 10.1061/(ASCE)CC.1943-5614.0000160. (C) 2011 American Society of Civil Engineers.

  • Details
  • Metrics
Type
research article
DOI
10.1061/(ASCE)CC.1943-5614.0000160
Web of Science ID

WOS:000291724300015

Author(s)
Bai, Y.  
Hugi, E.
Ludwig, C.
Keller, T.  
Date Issued

2011

Publisher

American Society of Civil Engineers

Published in
Journal of Composites for Construction
Volume

15

Issue

3

Start page

404

End page

412

Subjects

Durability

•

Fire protection

•

Fires

•

Glass fibers

•

Heating

•

Pultrusion

•

Water cooling systems

Editorial or Peer reviewed

REVIEWED

Written at

EPFL

EPFL units
CCLAB  
Available on Infoscience
May 30, 2011
Use this identifier to reference this record
https://infoscience.epfl.ch/handle/20.500.14299/67987
Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés