  4. Implementation of a scroll booster compressor into a single-stage air-water heat pump for peak winter day
 
conference paper

Implementation of a scroll booster compressor into a single-stage air-water heat pump for peak winter day

Zehnder, Michele
•
Schiffmann, Jürg Alexander  
•
Carré, Jean-Baptiste  
Show more
2010
Proceedings of the 23rd International Conference on Efficiency, Cost, Optimization, Simulation and Environmental Impact on Energy Systems
International Conference on Efficiency, Cost, Optimization, Simulation and Environmental Impact on Energy Systems

This paper shows an implementation of a scroll booster compressor mounted at the suction line of a single-stage air-water heat pump. The compressor selected to be used as booster is a beltdriven scroll compressor initially dedicated to automotive refrigeration. For the tests reported here, it is driven by an electrical motor and has been modified to obtain a lower built-in volume ratio. The computations for those modifications have been made with our own software called GeoScroll. Tests of the heat pump at A-11/W65 show a large improvement of the heat output, which is doubled (raising from 7.39 kW, in the normal single-stage configuration, up to 15.7 kW) while the COP decreases by less than 10% (from 2.08 to 1.89). This performance degradation is not due to bad performances of the booster compressor, that are at the level expected, but to a decrease of the evaporation pressure (1 bar, which is equivalent to 11 K), as the evaporator has not been designed for such heating powers. Even with working conditions outside its design range, the heat pump behavior with the booster has been proved to be very stable (the experiments were performed over few weeks). Furthermore, no oil accumulation has been noticed in the booster compressor, which is favorable to an integration of the device into existing heat pumps, currently in service. Indeed, it can be easily included into existing single-stage heat pumps with few adaptations. The concept is attractive in comparison to backup with heating devices, used in case of low temperatures, with a far better exergy efficiency and with contribution to the reduction of the electric demand peak.

  • Details
  • Metrics
Type
conference paper
Author(s)
Zehnder, Michele
Schiffmann, Jürg Alexander  
Carré, Jean-Baptiste  
Favrat, Daniel  
Date Issued

2010

Published in
Proceedings of the 23rd International Conference on Efficiency, Cost, Optimization, Simulation and Environmental Impact on Energy Systems
Volume

1

Subjects

Booster

•

Scroll compressor

•

Single-stage

•

Two-stage

•

Heat pump

•

Air/Water heat pump

Editorial or Peer reviewed

REVIEWED

Written at

OTHER

EPFL units
LENI  
Event nameEvent placeEvent date
International Conference on Efficiency, Cost, Optimization, Simulation and Environmental Impact on Energy Systems

Lausanne, Switzerland

June 14-17, 2010

RelationURL/DOI

IsPartOf

https://infoscience.epfl.ch/record/164962
Available on Infoscience
February 21, 2013
Use this identifier to reference this record
https://infoscience.epfl.ch/handle/20.500.14299/89027
Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés