  4. Heat recovery potential from ventilated passive and active facades
 
conference paper

Heat recovery potential from ventilated passive and active facades

Rahiminejad, Mohammad  
•
Khovalyg, Dolaana  
April 20, 2022
2022: CLIMA 2022 The 14th REHVA HVAC World Congress Proceedings
CLIMA 2022 The 14th REHVA HVAC World Congress

A ventilated air-space behind external claddings can potentially affect the thermal performance of the entire building structure. In particular, in the Building Integrated Photovoltaic (BIPV) facades, ventilated cavities are typically present between the PV panels and the walls of the building. The airflow in the cavity can remove the generated heat behind the active external cladding, which could be eventually used as an additional source for heat recovery. In this study, the heat recovery from a ventilated air-space behind passive (wood) and active (BIPV) facades are investigated using transient simulations. The numerical model used in this study is validated against experimental measurements carried out in a building prototype located in the Smart Living Lab in Fribourg (Switzerland). The original façade is made of wooden cladding that is separated from the wall core incorporating a ventilated cavity. To study the impact of façade type on the results, the external cladding is virtually replaced with typical polycrystalline PV panels. The analyses are performed for representative days in the winter and summer of 2021 using recorded weather data on the test building. The results are examined in terms of the temperature distribution of the layers in the wall assembly, heat flux through the indoor space, airspeed in the cavity, and heat flow in the air gap. The potentials for heat recovery per day of interest are also calculated and compared. It was shown that the heat recovery from the cavity behind the BIPV façade could become equal to 5341 kWh on a representative summer day, which is considerably higher compared to the value obtained for a passive cladding. The results highlight the potential for harvesting heat from the ventilated air gaps behind passive and active facades. The outcome of this study highlights the need for the integrated vision for energy-savings at the building scale. CLIMA 2022 conference, 2022: CLIMA 2022 The 14th REHVA HVAC World Congress

  • Files
  • Details
  • Metrics
Type
conference paper
DOI
10.34641/clima.2022.147
Author(s)
Rahiminejad, Mohammad  
Khovalyg, Dolaana  
Date Issued

2022-04-20

Publisher

TU Delft OPEN

Published in
2022: CLIMA 2022 The 14th REHVA HVAC World Congress Proceedings
Total of pages

7

Editorial or Peer reviewed

REVIEWED

Written at

EPFL

EPFL units
ICE  
Event nameEvent acronymEvent placeEvent date
CLIMA 2022 The 14th REHVA HVAC World Congress

CLIMA 2022

Rotterdam, The Netherlands

2022-05-22 - 2022-05-25

Available on Infoscience
September 24, 2022
Use this identifier to reference this record
https://infoscience.epfl.ch/handle/20.500.14299/190887
Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés