  4. Two-phase mini-thermosyphon electronics cooling: Dynamic modeling, experimental validation and application to 2U servers
 
research article

Two-phase mini-thermosyphon electronics cooling: Dynamic modeling, experimental validation and application to 2U servers

Lamaison, Nicolas  
•
Ong, Chin Lee  
•
Marcinichen, Jackson B.
Show more
2017
Applied Thermal Engineering

Gravity-driven cooling systems employing microchannel flow boiling can become a scalable and viable long term solution for the cooling of datacenter servers. In order to design this emerging type of cooling system, a new dynamic simulation tool using interconnected PDEs is described in the first part of the present paper followed by the validation of the modeling for both steady and dynamic regimes using a first-of-a-kind 15 cm-height thermosyphon test bench. A corrected error of 0.4 K was found for 7 different steady-state mean chip temperatures and heat load disturbances were predicted with the same 2-stage process presented here as the experimental results. The code was then used to predict the behavior of a mini-thermosyphon that would fit within the height of a 2U server. Multiple steady-state solutions were found with both stable and unstable operating states. A sensitivity study demonstrated that a 30% increase in the riser internal diameter led to 10-60% increase in the mass flow rate depending on the heat flux. Then, simulations with unbalanced heat loads showed that the flow gets self redistributed into the CPU with the highest heat load, e.g. 1.7 times larger flow rate for a heat flux 3 times larger. Finally, heat load and water coolant flow rate disturbances were also simulated and discussed. (C) 2016 Elsevier Ltd. All rights reserved.

  • Details
  • Metrics
Type
research article
DOI
10.1016/j.applthermaleng.2016.08.198
Web of Science ID

WOS:000388775600050

Author(s)
Lamaison, Nicolas  
Ong, Chin Lee  
Marcinichen, Jackson B.
Thome, John R.  
Date Issued

2017

Publisher

Pergamon-Elsevier Science Ltd

Published in
Applied Thermal Engineering
Volume

110

Start page

481

End page

494

Subjects

2U server

•

Cooling

•

Flow boiling

•

Thermosyphon

•

Microchannels

•

Dynamic modeling

Editorial or Peer reviewed

REVIEWED

Written at

EPFL

EPFL units
LTCM  
Available on Infoscience
January 24, 2017
Use this identifier to reference this record
https://infoscience.epfl.ch/handle/20.500.14299/133471
Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés