Scale limitations of gas bearing supported turbocompressors for vapor compression cycles

Schiffmann, J.  
•
Kontomaris, K.
•
Arpagaus, C.
Show more
January 1, 2020
International Journal of Refrigeration

An analysis of single-stage centrifugal compressors supported on dynamic, gas lubricated bearings for driving vapor compression cycles suggests that the maximum feasible compressor power is limited, primarily by the bearing load capacity, in the range from 80 kW to 250 kW. The analysis further suggests that the maximum feasible compressor power depends significantly on working fluid selection. Low-pressure fluids result in large impellers with good efficiency but heavy machines, the power of which is limited by the bearing load capacity. High-pressure fluids require small machines rotating at high speeds, the power of which is limited by the rotordynamic eigenfrequencies. Consequently, there is a family of fluids that allows maximization of the power range of gas bearing supported turbocompressors. Finally, the analysis suggests that the maximum compressor power can be expressed as a function of the reduced evaporation pressure, regardless of the working fluid choice. Maximum COP is reached at a reduced evaporation pressure decreasing nearly linearly from 0.20 to 0.09 as the temperature lift between the evaporator and the condenser increases from 20 K to 50 K. The feasible maximum compressor power increases with increasing specific compressor speed, bearing tip speed (NDm) and rotordynamic stability safety margin.

  • Details
  • Metrics
Type
research article
DOI
10.1016/j.ijrefrig.2019.09.019
Author(s)
Schiffmann, J.  
Kontomaris, K.
Arpagaus, C.
Bless, F.
Bertsch, S.
Date Issued

2020-01-01

Published in
International Journal of Refrigeration
Article Number

JIJR4535

Editorial or Peer reviewed

REVIEWED

Written at

EPFL

EPFL units
LAMD  
Available on Infoscience
October 7, 2019
Use this identifier to reference this record
https://infoscience.epfl.ch/handle/20.500.14299/161871
Logo EPFL, École polytechnique fédérale de Lausanne
  • Contact
  • infoscience@epfl.ch

  • Follow us on Facebook
  • Follow us on Instagram
  • Follow us on LinkedIn
  • Follow us on X
  • Follow us on Youtube
AccessibilityLegal noticePrivacy policyCookie settingsEnd User AgreementGet helpFeedback

Infoscience is a service managed and provided by the Library and IT Services of EPFL. © EPFL, tous droits réservés